Mfg Part Number: 10022975-104 | Alternate P/N: 10022975104 | Manufacturer: Honeywell International Inc |
NSN : 5925-00-899-4053 | NIIN : 008994053 | Item Name : circuit breaker |
CAGE Code : 94580 | FSC : 5925 Circuit Breakers |
Thank you for your continued interest in the 10022975-104 part currently available on National Stock Number Parts. Here, our customers will find our NSN RFQ Page for Circuit Breaker parts under FSC 5925 Circuit Breakers with the NSN 5925-00-899-4053, among others from the manufacturer Honeywell International Inc. For particular equipment, such as part number 10022975-104, the submission of a completed RFQ form will provide customers with a quote on any desired part in just 15 minutes or less. Upon receival, our expert market representatives will use your offered information to construct a quote paramount to your operations with rapid turnaround times and cost savings at our forefront.
As our robust supply chain stretches across the United States, Canada, and the United Kingdom, we are able to supply entities facing Aircraft on Ground (AOG) delays or other unique time constraints with expedited shipping on select NSN 5925-00-899-4053 items for immediate procurement. Operating as an AS9120B, ISO 9001:2015, and FAA AC 00-56B certified enterprise, products listed on our database are upheld to rigorous quality assurance testing, inspection, and cross-referencing before shipment. Functioning as the only independent distributor with a NO CHINA SOURCING pledge, you can depend on National Stock Number Parts for authentic 10022975-104 NSN part, which are listed alongside the CAGE Code 94580 by Honeywell International Inc.
MRC | Criteria | Characteristic |
---|---|---|
ABHP | OVERALL LENGTH | 2.600 INCHES NOMINAL |
ABKW | OVERALL HEIGHT | 0.625 INCHES NOMINAL |
ABMK | OVERALL WIDTH | 1.500 INCHES NOMINAL |
ADTV | CASE MATERIAL | METAL |
AKPX | POLE QUANTITY | 1 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES DC SINGLE LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 50.0 DC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 500.0 DC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS SINGLE LOCATION AND TIME DELAY SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | RESET |
CQJX | NOMINAL THREAD SIZE | 0.375 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.300 NOMINAL AT 125 PCT SINGLE LOCATION AND 0.060 NOMINAL AT 200 PCT SINGLE LOCATION |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND EXPLOSION PROOF |
PRMT | PRECIOUS MATERIAL | SILVER |
THSD | THREAD SERIES DESIGNATOR | UNEF |
TTQY | TERMINAL TYPE AND QUANTITY | 2 TAB, SOLDER LUG |